Sauna Heater Size Calculator

Calculate the right heater size (kW) for your sauna based on room dimensions, wall material, and insulation quality.

Room Details

Measurement Unit
Room Dimensions
Wall Material
Insulation Quality

Recommended Heater Size

6

kilowatts (kW)

Calculated need: 4.65.6 kW (ideal: 5 kW)

Room Volume

252 ft³

Adjusted Volume

252 ft³

Common Heater Sizes

3 kW 135165 ft³
4.5 kW 202.5247.5 ft³
6 kW ← Your size270330 ft³
8 kW 360440 ft³
9 kW 405495 ft³
10.5 kW 472.5577.5 ft³
12 kW 540660 ft³
15 kW 675825 ft³
18 kW 810990 ft³

Electrical Requirements (6 kW)

Circuit Breaker

30A

Voltage

240V

Wire Gauge (240V)

10 AWG

Amperage (240V)

25A

How to Size a Sauna Heater

Choosing the right sauna heater size is critical for performance, energy efficiency, and safety. An undersized heater will struggle to reach proper temperatures, while an oversized one wastes electricity and can overheat the room. The standard industry formula uses cubic footage as the primary input: approximately 1 kW of heater power per 50 cubic feet of sauna room volume.

However, raw cubic footage alone is not enough. Wall material and insulation quality significantly affect how much heat the room retains. A well-insulated cedar-lined sauna holds heat efficiently and requires less power, while a sauna with concrete walls, large glass panels, or poor insulation loses heat faster and needs a more powerful heater to compensate. Our calculator adjusts for these factors using industry-standard multipliers from major heater manufacturers like Harvia, Huum, and Finlandia.

Wall Material Impact

Wood-lined saunas (cedar, spruce, aspen, hemlock) are the gold standard because wood absorbs minimal heat and reflects it back into the room. Concrete, brick, and stone walls absorb significant thermal energy before the room reaches target temperature, effectively increasing the volume the heater must serve by 30–50%. Glass panels, increasingly popular in modern sauna designs, provide almost no insulation and require similar compensation. If your sauna has a glass door plus a glass wall section, factor in the glass multiplier.

Electrical Considerations

Most residential sauna heaters above 4.5 kW require a dedicated 240V circuit. Always hire a licensed electrician for installation and verify that your electrical panel has sufficient capacity for the heater's amperage draw. The National Electrical Code (NEC) requires that sauna heater wiring use a dedicated circuit with the appropriate wire gauge and breaker size. Our calculator provides general electrical guidance, but consult your electrician and the heater manufacturer's specifications for your exact installation.

Frequently Asked Questions

What size sauna heater do I need?

The general rule is 1 kW per 50 cubic feet of sauna room volume. For a standard 6×6×7 foot sauna (252 cubic feet), you would need approximately 5 kW. However, this should be adjusted upward for non-wood wall materials, glass panels, poor insulation, or rooms with high ceilings.

What happens if my sauna heater is too small?

An undersized heater will take much longer to reach target temperature, may never reach the highest temperatures (180–200°F), and will run continuously, increasing electricity costs and reducing the heater's lifespan. It's always better to size up slightly than to undersize.

Can a sauna heater be too powerful for the room?

Yes. An oversized heater can overheat the sauna too quickly, creating uncomfortable hot spots near the heater and an uneven temperature distribution. It can also pose a safety risk and wastes energy. If you're between sizes, going one size up is fine, but jumping two sizes is not recommended.

Do glass doors affect heater size?

Yes. A standard glass sauna door adds roughly the equivalent of 10–15 additional cubic feet to your calculation because glass has poor insulation compared to an insulated wood door. A full glass wall panel has an even larger impact. Our calculator accounts for this through the glass wall material multiplier.

What is the difference between 120V and 240V sauna heaters?

120V heaters (typically 1.5–4.5 kW) plug into a standard household outlet and are suitable only for small saunas under 200 cubic feet. 240V heaters (4.5–18 kW) require a dedicated circuit installed by an electrician but heat faster, reach higher temperatures, and are the standard for most home and commercial saunas.